Single phase high-disenty online ups (3-10kva)
DTL Series · Online Double Conversion · Single phase UPS for critical loads (3kVA / 6kVA / 10kVA).
Model: DTL Series (DTL11-3K / DTL11-3KL / DTL11-6KL / DTL11-10KL)
Capacity
3kVA / 6kVA / 10kVA
Topology
Online Double Conversion
Input
L + N + PE · 208/220/230/240VAC · 110–300VAC range
Output
208/220/230/240VAC · Voltage accuracy ±1% · 0ms transfer
| Parameter | Value |
|---|---|
| Series | DTL |
| Capacity | 3kVA / 6kVA / 10kVA |
| UPS technology | Online Double Conversion |
| Input wiring | L + N + PE |
| Rated input voltage | 208/220/230/240VAC |
| Input voltage range | 110–300VAC |
| Input frequency range | 40–70Hz |
| Input power factor | ≥0.98 (3kVA) · ≥0.99 (6–10kVA) |
| Rated output voltage | 208/220/230/240VAC |
| Output voltage accuracy | ±1% |
| Output frequency range | 50/60±6Hz (sync) · 50/60Hz ±0.1% (constant frequency mode) |
| Output power factor | 0.9 |
| THDu | ≤2% @ 100% linear load · ≤5% @ 100% non-linear load |
| Switching time | 0 ms |
| Overload | 102%–110%: 30 min · 111%–130%: 10 min · 131%–150%: 30 s · >150%: 200 ms |
| Battery type | VRLA |
| Charging current | 1A · 5A (long backup model) · 1–12A adjustable |
| Battery voltage | 72VDC (DTL11-3K) · 96VDC (DTL11-3KL) · 192–240VDC (DTL11-6KL / DTL11-10KL) |